“ROBOT 165 – 232 DAC Series” offers very efficient and service-friendly solutions with long life components & system. With the integrated inverter module, it is ideal for medium size businesses who need energy saving. It can be used in every industry sector. Shipped as one unit ready for start-up / commissioning.
* Valid IE class efficiency, IP55/F, PTC protected Electric Motor
* Extra PT100 protection on motor winding; as standard
* 1:1 Direct Drive System
* Patented technology, natural rubber elastic coupling element. Long product life, easy to disassemble quickly.
* Variable Speed / Speed regulated Operating Mode
* Energy-saving operating mode with a stable pressure point at discharge
* Protection of compressor unit against peak starting current
* Protection of compressor components with softstarting
* Efficient operation: fast response to fluctuations in compressed air demands
* Control and monitoring of Motor PT100 temperature through inverter panel
* Specially selected for every model capacity; Made in Europe
* Optimum minimum-maximum airend speed range according to the safe-zone of the motor
* Optimum capacity & minimum shaft power
* Max.Pressure 16 barg
* Long-lasting and quality-made design with new generation bearing selection.
* No pressure-loss at discharge of airend with original diameter piping
* Direct connection with original victualic © couplings to air/oil separator tank with minimal elbows
* Includes: inverter set, fan contactor, motor protection switch & fuse, control transformer (24V)
* Emergency stop switch, on/off switch, control panel (CPU), LCD digital monitor.
* Microprocessor-controlled electronic control/command module with Start/Stop mode, total or on-load operating time,
pressure regulation, system pressure and oil temperature, protection functions during alarms.
* Automatic operating mode which saves energy
* Message monitoring as text in different languages
* Up to 24 languages
* 3.2″ color LED display monitor
* Sequence operation model up to 8 compressor units
* 10 different user setting profiles
* Password protection to access parameters
* 4 programmable relays
* Integrated main motor and fan motor overcurrent protection
* Display of average value of phase voltages
* 8 qty. maintenance programming
* 50 qty. real-time logs
* Read-write-access parameters, compatible with SCADA systems
* RS485, Airbus, ModbusRTU communication protocols
* Compatible with multi-compressor automation systems for energy algorithms (DCO, P4, SX, XC)
* Ready for Industry 4.0 / IOT configurations
* Remote control/command option
* Compatible with 2014/35/EU and 2014/30/EU: European EMC and LVD directives.
* Robust and resistant ABS plastic cover
* High Volume Air Cooler resistant to harsh conditions (minimum load to Dryer)
* New Generation High volume Robust Oil Cooler resistant to thermal expansions and vibrations (optimum Delta T)
* 1 or 2 qty. Independent silent motor-integrated Inlet Axial Fans for effective cooling; depending on the model
* Quality and long-lasting compressor oil
* Less than 3 ppm oil residual in the discharge compressed air
* Optional integrated heat recovery system
* Original design and production by Sarmak: Vertical Air/Oil Tank certified by TÜV-SÜD/Germany
* Service-friendly, Vertical type Air/Oil separator filter element
* Inlet air filter, intake valve, safety valve, minimum pressure checkvalve, factory filled oil,
* Sound and vibration insulated canopy, chassis.
Model | Maximum Operating Pressure | Free Air Delivery | Nominal Motor Power | Sound Level from 1mt (dBA) | Compressed Air Connection | Dimensions | Total Weight (kg) | |||||||
(bar g) | (psi g) | Minimum | Maximum | (kW) | (HP) | Length (mm) | Width (mm) | Height (mm) | ||||||
(m3/min) | (cfm) | (m3/min) | (cfm) | |||||||||||
ROBOT 165 DAC | 7.5 | 108.7 | 6.30 | 222.4 | 16.25 | 573.8 | 90 | 125 | 76 | 2″ | 2.655 | 1.610 | 1.860 | 2.500 |
ROBOT 166 DAC | 10 | 145.0 | 6.83 | 241.2 | 13.95 | 492.6 | 90 | 125 | 76 | 2″ | 2.655 | 1.610 | 1.860 | 2.500 |
ROBOT 167 DAC | 13 | 188.5 | 6.67 | 235.5 | 11.90 | 420.2 | 90 | 125 | 76 | 2″ | 2.655 | 1.610 | 1.860 | 2.500 |
ROBOT 180 DAC | 7.5 | 108.7 | 6.50 | 229.5 | 17.45 | 616.2 | 90 | 125 | 77 | 3″ | 2.655 | 1.610 | 1.860 | 2.920 |
ROBOT 181 DAC | 10 | 145.0 | 7.05 | 248.9 | 15.47 | 546.3 | 90 | 125 | 77 | 3″ | 2.655 | 1.610 | 1.860 | 2.920 |
ROBOT 182 DAC | 13 | 188.5 | 6.88 | 242.9 | 13.45 | 474.9 | 90 | 125 | 77 | 3″ | 2.655 | 1.610 | 1.860 | 2.920 |
ROBOT 210 DAC | 7.5 | 108.7 | 7.39 | 260.9 | 20.77 | 733.4 | 110 | 150 | 77 | 3″ | 2.655 | 1.610 | 1.860 | 3.060 |
ROBOT 211 DAC | 10 | 145.0 | 7.12 | 251.4 | 18.63 | 657.9 | 110 | 150 | 77 | 3″ | 2.655 | 1.610 | 1.860 | 3.060 |
ROBOT 212 DAC | 13 | 188.5 | 7.03 | 248.2 | 16.21 | 572.4 | 110 | 150 | 77 | 3″ | 2.655 | 1.610 | 1.860 | 3.060 |
ROBOT 230 DAC | 7.5 | 108.7 | 7.05 | 248.9 | 22.87 | 807.6 | 132 | 180 | 78 | 3″ | 2.905 | 1.760 | 1.860 | 3.260 |
ROBOT 231 DAC | 10 | 145.0 | 6.70 | 236.6 | 20.10 | 709.8 | 132 | 180 | 78 | 3″ | 2.905 | 1.760 | 1.860 | 3.260 |
ROBOT 232 DAC | 13 | 188.5 | 6.90 | 243.6 | 17.45 | 616.2 | 132 | 180 | 78 | 3″ | 2.905 | 1.760 | 1.860 | 3.260 |
STANDARDS : FREE AIR DELIVERY-PRESSURE (CAGI PNEUROP PN2CPTC2-ISO 1217), SOUND LEVEL (CAGI PNEUROP PN8NTC2), QUALITY ASSURANCE (ISO 9001:2015).
GUARANTEED TOLERANCES : UNDER NOMINAL CONDITIONS, THE INDICATED FREE AIR DELIVERY (m3/min) AND SPECIFIC POWER (kW X min / m3) ARE COMPLIANT WITH ISO 1217-ANNEX C STANDARDS.
MANUFACTURED IN SARMAK MAKINA A.S. FACILITIES, NEW GENERATION ROBOT 165-232 DAC _ SERIES COMPRESSORS ARE PRODUCED WITH THE UTMOST IMPORTANCE AND STATE-OF-THE-ART TECHNOLOGY. EACH AND EVERY UNIT IS TESTED IN DETAIL FOR
FUNCTIONALITY AND PERFORMANCE IN OUR MODERN TEST CENTER DESIGNED ACCORDING TO ISO STANDARDS. AFTERWARDS, EACH UNIT IS CHECKED BY OUR EXPERIENCED ENGINEERS FOR SARMAK QUALITY ASSURANCES. FINALLY, THE UNIT IS
PACKAGED AND SHIPPED FOR START-UP AT CUSTOMER’S SITE.
Piping Material Features Comparison |
|||
Piping Features | Stainless Steel(Type 304L) | Mild Steel | Blue anodized Aluminum Alloy |
Weight (Dia 6inch, Length 6m) | 127.2 | 169.6 | 29.142 |
Corrosion Resistant | Yes | No | Yes(100%) |
Pressure drop (Dia 2 inch Length= 20m,Airflow=3 cubic metres/Minute, Pressure=10 bar) | 0.25 | 0.4 Bar | 0.1 |
Energy Efficiency | High | Low-moderate | High( Potential Cost savings of 34%) |
Mechanical Strength | Very Strong | Very Strong | Strong |
High-Temperature Rating | Yes | Yes | Yes |
Installation Ease | Less Difficult | Difficult | Easy(High Flexibility and Modularity) |
Installation Time | Approx 6 feet length per hour | Approx 6 feet length per hour | Approx 45 feet Length per hour |
Work Hours/Manpower Required for a 2″ pipe and a 3000 feet piping | Approx 600 man-hours/8 men for 2 weeks | Approx 600 man-hours/8 men for 2 weeks | Approx 100 man-hours /8 men for less than 2 days |
Annual Cost(Installation, Commissioning, and operation) | Approx 3000 dollars | Approx 7820 dollars | Approx 1300 dollars |
Installation Cost Material%/Labor% | 30% / 70% | 25% / 75% | 80% / 20% |
Surface roughness | 0.03 | 0.05 | 0.001 |
Special Tools Required (welder, threader, groove cutter) | Yes | Yes | No |
Air Quality | High(Should the application require it, these pipe systems can help meet the requirements of ISO 8573-1: 2010 air quality standards. | Low( Not according to !SO 8573-2010 air quality standards) | High(Should the application require it, these pipe systems can help meet the requirements of ISO 8573-1: 2010 air quality standards. |
Cost per meter | Almost 2 less than Aluminum | 3 Times less than Aluminum | 163.64 Dollars(Parker Transair) |
Life Span( Will vary according to environmental factors, Pipe design, and Pipe grade. | 30 years | 40 years | 20 years |
Initial Cost of installations | Material : 30% Labor:70% | Material : 25% Labor:75% | Material : 80% Labor:20% |
Maintenance | Difficult(Accumulation of rust under pipes and fittings which travels to machinery, may require preventive maintenance every week) | Difficult (Accumulation of rust under pipes and fittings which travels to machinery may require preventive maintenance every 3-4 days) | Easy (No accumulation of rust, may require preventive maintenance every 4 Weeks) |